Cooling plant case

Solar manufacturing cooling plant

A large industrial plant with low-temperature chillers, heat-recovery chillers, cooling towers, pumps, and plate heat exchangers was evaluated through comparable operating days.

Average savings
21.29%

Average result across the comparable-day review.

20-day comparable result
24.51%

Reported savings rate over the 20 operating-day comparison.

Major equipment
56 units

Chillers, towers, pumps, and plate heat exchangers in scope.

Plant profile

Large industrial cooling plant with heat recovery

The cooling source used centrifugal chillers. The system combined five low-temperature chillers including one standby unit, four heat-recovery centrifugal chillers with three duty and one standby unit, seventeen cooling towers, nine chilled-water pumps, nine condenser-water pumps, four heat-recovery pumps, four medium-temperature circulation pumps, and four plate heat exchangers.

Equipment

Major equipment

Cooling towers were connected in parallel. Chilled-water and condenser-water pumps used one-to-one pairing with chillers, while heat-recovery pumps were connected in parallel.

EquipmentQuantitySpecificationStatus
Low-temperature centrifugal chillers38791 kW cooling capacity / 1527 kW power / High-voltage supply / 0.61 kW/ton rated efficiency / Two fixed-speed, one variable-speedInstalled low-temperature group
Low-temperature centrifugal chiller17032 kW cooling capacity / 1229 kW power / High-voltage supply / 0.61 kW/ton rated efficiencyInstalled low-temperature group
Low-temperature centrifugal chiller14220 kW cooling capacity / 725.2 kW power / High-voltage supply / 0.60 kW/ton rated efficiencyStandby included in low-temperature group
Heat-recovery centrifugal chillers48791 kW cooling capacity / 1464 kW cooling power / 10253 kW heating capacity / 1465 kW heating power / High-voltage supply / 0.59 kW/ton cooling / 0.59 kW/ton heating rated efficiency3 duty / 1 standby
Chilled-water pumps71410 m³/h flow / 47.5 m head / 250 kW / Integrated VFDOne-to-one chiller pairing
Chilled-water pump11200 m³/h flow / 50 m head / 220 kW / Integrated VFDOne-to-one chiller pairing
Chilled-water pump1720 m³/h flow / 50 m head / 160 kW / Integrated VFDOne-to-one chiller pairing
Heat-recovery pumps41410 m³/h flow / 47.5 m head / 250 kW / Integrated VFDParallel connection
Medium-temperature circulation pumps4650 m³/h flow / 48 m head / 132 kW / Integrated VFDIncluded in plant scope
Cooling towers17Dual-speed fan / 30 kW / 22 kWParallel connection
Condenser-water pumps91900 m³/h flow / 28 m head / 185 kW / Integrated VFDOne-to-one chiller pairing
Plate heat exchangers4Included in heat-exchange plant scopeIncluded in plant scope

Evaluation scope

Evaluation scope

Comparison method
Comparable-day analysis.
Matching variables
Average dry-bulb temperature, average wet-bulb temperature, production output, and average load.
Operating window
Twenty operating days were included in the comparable-day review.

Calculation detail

Matched-day energy-savings calculation

Comparable-day basis
Days matched by weather, production output, and average load.
Matched-day pair
Jun 20 baseline operation compared with Jul 13 AI operation.
Baseline-day total energy
102,799.1 kWh
AI-day total energy
82,833.7 kWh
Matched-day energy savings
19.42%
20-day energy savings
491,304 kWh
20-day average plant efficiency improvement
21.29%
  1. 1. Comparable days were matched by weather, production output, and average load.
  2. 2. Jun 20 baseline and Jul 13 AI operation form the highlighted matched-day pair.
  3. 3. Matched-day energy savings = (102,799.1 - 82,833.7) / 102,799.1 x 100% = 19.42%.
  4. 4. The 20-day operating window reports 491,304 kWh measured energy savings.
  5. 5. The 20-day average plant efficiency improvement is reported as 21.29%.

Case result

Matched-day energy savings
=Baseline-day total energy-AI-day total energyBaseline-day total energy*100%
=102,799.1-82,833.7102,799.1*100%
=19.42%

Daily operating data

Daily operating data

The daily record includes chiller, pump, tower, total energy, dry-bulb temperature, wet-bulb temperature, production output, average load, and plant efficiency. Jul 15 is retained as a production-only partial record and excluded from the scatter plot.

Daily total energy vs outdoor average temperature

69000883251076501269751463002527303234Outdoor average temperature CkWh/day
Baseline controlAI controlTransition day
ModeDateChiller kWhChilled-water pump kWhCondenser-water pump kWhCooling tower kWhTotal energy kWhOutdoor average temp CAverage wet-bulb temp CProduction outputAverage loadPlant efficiency kW/ton
Baseline controlJun 2075070.909583.508429.809714.9010279929.9224.5268885413045.01.15
Baseline controlJun 2176447.509467.608271.509957.6010414426.3225.4457102812933.01.18
Baseline controlJun 2273883.409225.107455.209858.1010042228.8524.9052489312680.01.15
Baseline controlJun 2373952.908472.807017.6010090.009953329.5724.3553413413445.01.12
Baseline controlJun 2470409.308361.507082.609211.309506528.2424.0550628612298.01.17
AI controlJun 2556407.804672.703709.507058.607184927.9422.7738275311638.00.89
AI controlJun 2654539.604510.403662.406480.606919328.3721.8454949411605.00.86
AI controlJun 2766422.504832.904801.308020.808407828.1022.2669334812228.01.00
AI controlJun 2872261.403256.505137.208838.508949425.4023.63114440414007.00.92
AI controlJun 2979760.405428.103904.607252.209634526.9624.50122144914769.00.94
AI controlJun 3085812.205596.505596.508331.6010518929.8625.52119226715525.00.97
AI controlJul 179121.005187.504399.506976.009568427.9424.19126951214646.00.97
AI controlJul 253493.505149.704369.406976.006998926.2323.00111368913940.00.92
AI controlJul 394986.006039.005932.007987.0011494429.4225.12123092917350.00.95
AI controlJul 498116.006411.007840.005775.0011814527.9025.45124055718045.00.95
AI controlJul 5119534.007902.505574.909502.5014251432.6226.91130383220199.01.02
AI controlJul 6119640.407628.106410.208428.2014210731.6927.24130046420256.01.02
AI controlJul 7125835.007264.006160.005853.8014511333.6327.50130583320824.01.00
AI controlJul 8126807.507072.606539.205708.2014612832.5527.59141456120974.01.00
AI controlJul 9102834.106083.206083.205296.1012029726.8825.22130795018145.00.95
AI controlJul 1087367.805571.903722.305203.3010186525.7523.94101098116011.00.93
AI controlJul 1169052.003093.005083.003843.008107125.3823.1853645613644.00.90
AI controlJul 1270339.003141.406052.005265.008479726.4025.0938403913541.00.93
AI controlJul 1369491.002999.605468.804874.308283428.6525.8728953513327.00.92
AI controlJul 1463633.003599.103931.005559.007672226.5525.4721071011368.41.02
Transition dayJul 15189780